Chroma
Chroma 6512
AC Source, 1.2KVA, 0-300V, 15 - 2 kHz, 1 Phase
10 V bis 1100 V DC Messbereich Spannung
100 µA bis 20 mA Messbereich Strom
±0,5 % ± 5 Digits Genauigkeit
100 MΩ bis 200 GΩ Isolationswiderstand
50 V, 100 V, 250 V, 500 V, 1000 V (einstellbar) Prüfspannung

| Attribut | Wert |
|---|---|
| Messbereich Spannung | 10 V bis 1100 V DC |
| Messbereich Strom | 100 µA bis 20 mA |
| Genauigkeit | ±0,5 % ± 5 Digits |
| Isolationswiderstand | 100 MΩ bis 200 GΩ |
| Prüfspannung | 50 V, 100 V, 250 V, 500 V, 1000 V (einstellbar) |
| Anzeige | 4½-stelliges LCD-Display |
| Schnittstellen | RS-232, GPIB (IEEE-488) |
| Betriebstemperatur | 0 °C bis 40 °C |
| Stromversorgung | 100–240 V AC, 50/60 Hz |
| Abmessungen (B × H × T) | 215 mm × 88 mm × 350 mm |
Chroma 6512 Options:
- 6512 - A650001 - Remote Interface for Model 6500 Series (External V Reference, RS-232 interface, Printer Interface, GPIB Interface, Special I/O Port, System I/O Port)
- 6512 - A650002 - 19" Rack Mounting Kit for Model 6512/6520/6530
- 6512 - A650003 - Softpanel for Model 6500 Series
- 6512 - A610004 - Universal Socket Center for Model 6512/6520/6530/6560 Series
- 6512 - A600009 - GPIB Cable (200cm)
- 6512 - A600010 - GPIB Cable (60cm)
| Model | 6512 |
|---|
Chroma 6512 AC Power Source The Chroma 6512 Programmable AC Power Source delivers the right solution to simulate all kinds of normal/abnormal input conditions and measure the critical characteristics of the products under test. It can simulate all kinds of power line disturbances such as cycle dropout, transient spike, brown out, phase angle, voltage and frequency ramp up (ramp down), etc. For the product tests under AC line distortion conditions, clipped sine wave can be generated with 0% to 43% distortion and amplitude from 0% to 100%. The Chroma 6512 also has built in Direct Digital Synthesis (DDS) Waveform Generator to provide user programmable high precision waveforms. The input AC to DC stage in the Chroma 6512 AC Source incorporates a modern power factor correction circuit to increase the input power factor more than 0.98 to meet the IEC regulations. . It reduces the input cur requirement and raises the efficiency up to over 80%. It is suitable for commercial applications (47-63Hz) such as avionics, marine, and military applications at 400Hz or higher frequency or for electrical motor, air conditioner test applications at 20Hz. The Chroma 6512 has 16-bit precision measurement circuits to offer precision and highspeed measurements for Vrms, Irms, Ipk+, Ipk-, power, frequency, crest factor, power factor, inrush cur, VA, and VAR. Specifications of the Chroma 6512 AC Power Source includes: See Datasheet for Full Specifications




