Megger TTR330A

| Attribute | Value |
|---|---|
| Turns Ratio Measurement Range | 0.8 to 10,000 |
| Turns Ratio Accuracy | ±0.1% of reading |
| Test Voltage | 8 V AC (selectable: 2 V, 4 V, 8 V) |
| Excitation Frequency | 50 Hz / 60 Hz (selectable) |
| Phase Displacement Measurement | 0° to 360° with ±0.1° accuracy |
| Excitation Current Measurement Range | 0 to 600 mA |
| Display | Backlit graphical LCD display |
| Power Supply | 115/230 V AC, 50/60 Hz or internal rechargeable battery |
| Data Storage | Up to 3,000 test records with USB data transfer |
| Operating Temperature Range | -20°C to +55°C (-4°F to +131°F) |
Megger TTR330A Options:
- TTR330A - TTR330A - Three-Phase TTR with PowerDB ONBOARD
- TTR330A - -47 - 230V operation fuse and 50Hz calibration (for accurate phase deviation)
| Model | TTR330A |
|---|
The Megger TTR330A is engineered for rapid, precise turns ratio testing of complex three-phase transformers, including units with multiple tap changers and bushing CTs. It operates between -20°C to +50°C, featuring a 12-inch sunlight-readable touch controller and built-in 2-inch printer. The device stores up to 100,000 test results and includes a safety shutdown function for data protection during power interruptions.
Designed for substation or manufacturing use, it accurately measures turns ratio and phase deviation to detect core faults and shorted turns. Results can be printed or exported to a PC for detailed analysis.
Testwall can supply the used Megger TTR330A, fully tested. With expert support and global delivery, Testwall ensures high-performance instrumentation with unmatched reliability and service quality. Please contact us directly if you need calibration or repair of the Megger TTR330A.